Generator Sizing Calculator: What kVA Generator Do You Need?

List your appliances with their running watts, starting watts and quantity. You will see the running load, the peak load including motor starting surges, and the generator size in kW and kVA to buy.

Last reviewed

Appliance 1
W
W
Appliance 2
W
W
Appliance 3
W
W
Appliance 4
W
W
% of rating

The appliances shown are placeholders. Replace them with the watts printed on your own appliances’ nameplates or manuals.

Generator size

7.71 kVA

6.17 kW at a power factor of 0.8; round up to the next size sold

Running load
1,935 W
Peak load
4,935 W
Extra starting surge
3,000 W
Running load in kVA
2.42 kVA

The largest surge is appliance 2. Start your biggest motor first, with the others off, so the surges do not add up.

Check the starting watts on the appliance label or in its manual. Air conditioners, pumps and compressors can need several times their running watts to start.

Why generator sizing needs two numbers per appliance

A generator has to cope with two loads. The first is the running load, what everything draws while it is on. The second is the starting surge. A motor in an air conditioner, a fridge, a water pump or a compressor draws several times its running power for a moment as it starts. A generator that covers the running load but not the surge will stall or trip when the compressor kicks in.

So the method uses two figures for each appliance, both printed on its nameplate or in its manual: the running watts and the starting watts. For a light bulb or a heater the two are the same, so leave the starting watts blank.

The calculation

  1. Running load = the sum of running watts × quantity.
  2. Peak load. If you will switch motors on one at a time, the peak is the running load plus the largest extra surge of any single appliance. The extra surge is its starting watts minus its running watts, because its running watts are already in the total. If everything might start at once, the peak is the sum of all starting watts × quantity, which is the safer, larger figure.
  3. Generator kW = peak load ÷ the loading you allow. If you do not want to run the generator beyond 80% of its rating, divide by 0.8.
  4. Generator kVA = generator kW ÷ power factor. Generators are rated in kVA, and a rating of 0.8 power factor is the usual assumption, so kVA is kW divided by 0.8.

The Omni Calculator generator-wattage tool uses the same ideas: it adds up running and surge watts, assumes generator power equal to the total surge, converts to kVA by dividing by a power factor that defaults to 0.8, and then allows for an operating capacity that defaults to 70%. Our calculator lets you choose the loading yourself and offers both ways of counting the surge.

Worked example

A small home wants to run a fridge (150 W running, 450 W starting), one air conditioner (1,500 W running, 4,500 W starting), three fans (75 W each) and six lights (10 W each). These are example figures, not recommendations.

  • Running load = 150 + 1,500 + 3 × 75 + 6 × 10 = 1,935 W, which is 2.42 kVA at a power factor of 0.8.
  • The largest extra surge is the air conditioner: 4,500 − 1,500 = 3,000 W.
  • Peak load with motors starting one at a time = 1,935 + 3,000 = 4,935 W.
  • Generator kW at an 80% loading = 4.935 ÷ 0.8 = 6.17 kW. As kVA = 6.17 ÷ 0.8 = 7.71 kVA.

Choose the next size sold above that. If every motor could start at the same moment, the peak is 450 + 4,500 + 225 + 60 = 5,235 W, which needs 8.18 kVA.

Generator size for a given peak load

At a power factor of 0.8 and an 80% loading.

Peak load Generator kW Generator kVA
2,000 W 2.50 3.13
3,000 W 3.75 4.69
4,000 W 5.00 6.25
5,000 W 6.25 7.81
8,000 W 10.00 12.50

Points to check

  • Use nameplate values. The wattages in the boxes when the page opens are placeholders. Read the label on each of your appliances or find the figure in its manual.
  • Inverter appliances may surge less. Their starting watts can differ from a conventional compressor of the same size. Use the manufacturer’s figure for each one.
  • Do not size to the minute. Leave room for appliances you will add later. A generator loaded close to its rating has no room for a surge you did not plan for.
  • Cost. A larger generator costs more to buy. Size it for what you need, with the margin above, rather than for the largest unit you can afford.
  • Safety. Install and connect a generator as the maker describes, outdoors and with a proper changeover switch, and ask a qualified electrician.

Related tools: the home battery sizing calculator, the electricity cost calculator, the watts to amps calculator and the amps to watts calculator.

Frequently asked questions

What size generator do I need?

Add the running watts of everything you will run, add the largest starting surge of any one motor, divide by how heavily you are willing to load the generator, and then divide by the power factor to get kVA. The calculator does each step for your own list of appliances.

What are running watts and starting watts?

Running watts are what an appliance draws while it operates. Starting watts, also called surge watts, are the higher draw for the first moments of a motor starting. Both are on the appliance label or in its manual. For lights and heaters the two are the same.

How do I convert kW to kVA?

Divide the kW by the power factor. Generators are commonly rated at a power factor of 0.8, so a 6.17 kW load needs about 7.71 kVA. If your generator states a different power factor, enter it in the calculator and the result changes.

Should motors start one at a time or together?

If you can control the order, starting the largest motor first with the rest off means only one surge counts. If several motors may start at once, such as after a power cut with everything switched on, count every surge. That gives the larger, safer size.

Why keep the load below 100% of the rating?

A margin leaves room for appliances you add later and for surges you did not plan for. The calculator divides the peak load by the loading you choose, 80% by default, so a lower percentage gives a larger generator. Omni’s tool defaults to 70%.