Watts to Amps Calculator (DC, AC and Three-Phase)

Enter the power and the voltage. Choose DC, single-phase or three-phase AC, and for AC the power factor, to get the current in amps.

Last reviewed

watts
volts

Current

12.5 A

apparent power 1,500 VA

Formula
W = A × V × PF
Power in kilowatts
1.5 kW

This is arithmetic from the numbers you enter. Check the rating plate and ask a qualified electrician about wiring, fuses and breakers. This page is information, not electrical advice.

The formulas

Current in amps comes from power in watts and voltage in volts:

Supply Amps
DC, or a simple resistive heater or bulb A = W ÷ V
AC, single phase A = W ÷ (V × PF)
AC, three phase (balanced load) A = W ÷ (√3 × V × PF)

W is the power in watts, V the voltage and PF the power factor, a number from 0 to 1 that says how much of the apparent power does useful work. For three phase, V is the voltage between two lines and A is the current in each line. These are rearrangements of P = IV, and of P = I × V × cos φ for AC, from the OpenStax physics texts. A load with a lower power factor draws more current for the same watts.

Worked examples

  • A 60 W bulb on 120 V: 60 ÷ 120 = 0.5 A. This is the example OpenStax gives for P = IV.
  • A 1,500 W heater on 120 V DC or resistive AC: 1,500 ÷ 120 = 12.5 A.
  • A 2,400 W single-phase motor on 230 V with a power factor of 0.9: 2,400 ÷ (230 × 0.9) = 2,400 ÷ 207 = 11.594 A. The apparent power is 2,400 ÷ 0.9 = 2,666.67 VA.
  • A 10 kW three-phase load at 400 V and a power factor of 0.9: 10,000 ÷ (√3 × 400 × 0.9) = 16.038 A in each line.
  • A 3 kW heater on 230 V: 3,000 ÷ 230 = 13.04 A.

Amps for common loads (power factor 1)

Watts At 120 V At 230 V At 240 V
100 0.83 0.43 0.42
500 4.17 2.17 2.08
1,000 8.33 4.35 4.17
1,500 12.5 6.52 6.25
2,000 16.67 8.7 8.33
3,000 25 13.04 12.5

The effect of the power factor (2,400 W, 230 V, single phase)

Power factor Amps
1 10.43
0.9 11.59
0.8 13.04
0.7 14.91

Why the power factor matters

The same real power at a lower power factor needs more current. A 2,400 W motor at a power factor of 1 would draw 10.43 A on 230 V; at 0.7 it draws 14.91 A. Cables, fuses and generators carry the current, which is why equipment is often rated in VA as well as watts. The calculator shows the apparent power for AC.

Common mistakes

  • Dividing by the voltage only for a motor. For AC loads with a power factor below 1, the current is higher than watts divided by volts.
  • Mixing up line and phase voltage on a three-phase supply. The formula uses the line-to-line voltage.
  • Using the nameplate watts as electrical input. A motor rated 2,400 W of output draws more than that from the supply, because of losses.
  • Treating the result as wiring advice. Fuses, breakers and cables are chosen under local rules. Ask a qualified electrician.

To go the other way use the amps to watts calculator. For other power units, see the power converter, and for the brightness side of a bulb, the lumens to watts converter.

Three-phase and other cases

For direct current, and for a single-phase supply with a power factor of 1, the current is the power divided by the voltage. A 1,500 W heater on 120 V draws 1,500 ÷ 120 = 12.5 A, and a 60 W lamp on 12 V draws 5 A.

For a three-phase supply the current in each line is the power divided by √3 × the voltage × the power factor. A 10 kW motor on 400 V at a power factor of 0.9 draws 10,000 ÷ (1.732 × 400 × 0.9) = 16.04 A. Use the line-to-line voltage in this formula.

These are the loads the equipment draws. A cable, a socket or a fuse must be rated above the current, so do not size one from the watts on a label alone, and ask a qualified electrician about any mains wiring.

How it is calculated

The power is divided by the voltage in 40-digit decimal arithmetic. For three phase, the voltage is first multiplied by √3 (1.7320508075688772…). For AC the divisor also includes the power factor. Only the figure displayed is rounded.

Frequently asked questions

How do I convert watts to amps?

Divide watts by volts. For DC and resistive loads: 1,500 W ÷ 120 V = 12.5 A. For single-phase AC also divide by the power factor, and for three-phase AC divide by √3 × volts × power factor.

How many amps is 1,000 watts?

At 120 V it is 8.33 amps, at 230 V it is 4.35 amps and at 240 V it is 4.17 amps, in each case for a power factor of 1. A lower power factor needs more current for the same watts.

What power factor should I use?

Use 1 for a resistive load such as a heater or incandescent bulb. For motors and many electronic loads use the figure on the rating plate or from the manufacturer, as it is below 1. The calculator allows 0.01 to 1.

How do I convert watts to amps in three-phase?

Divide the watts by √3 (1.732), the line-to-line voltage and the power factor. A 10 kW load at 400 V and a power factor of 0.9 draws 16.038 A in each line.

Does a higher voltage mean fewer amps?

Yes, for the same watts. A 2,400 W heater draws 20 A at 120 V and 10.43 A at 230 V, since current is power divided by voltage.