Voltage Drop Calculator for Copper Cable
Enter the supply voltage, the current, the one-way length and the wire size. You get the voltage lost in the cable, the voltage left at the load and the smallest size that keeps the drop within your limit.
Last reviewed
Voltage drop
2.9 V (2.41%)
117.1 V arrives at the load, on 12 AWG copper
- Resistance of the wire
- 1.932 Ω per 1,000 ft
- Resistance of the run
- 0.1932 Ω
- Power lost in the cable
- 43.5 W
- Smallest size within 3%
- 12 AWG
Only the resistance of the copper is counted. The size shown is for the voltage drop alone: the cable must also be big enough to carry the current safely, and wiring rules set that separately. Have a qualified electrician check any real installation.
What voltage drop is
Wire is not a perfect conductor. Current flowing along a cable loses a little voltage on the way, and the longer and thinner the cable, the more it loses. The loss shows up as lower voltage at the load and as heat in the cable. A lamp dims, a motor labours, a charger takes longer. Voltage drop is the voltage lost between the supply and the load.
The formulas
The voltage drop in a cable is the current times its resistance:
- DC and single phase AC: drop = I × R × 2L, where R is the resistance of the wire per unit length and L the one-way length. The factor 2 is there because current goes out and comes back.
- Three phase AC: drop = √3 × I × R × L, the line-to-line voltage drop in a balanced load.
The percentage drop is the drop divided by the supply voltage, and the voltage at the load is the supply voltage less the drop. Power lost in the cable is I² × the resistance of each conductor: 2 conductors for DC and single phase and 3 for three phase.
Where the wire resistance comes from
The calculator works the resistance out instead of looking it up:
- Cross-section. The American wire gauge diameter is d = 0.127 mm × 92^((36 − n) ÷ 39), where n is the gauge number (00, 000 and 0000 are n = −1, −2, −3). The area is π ÷ 4 × d². A kcmil size has an area of 1,000 × kcmil × π ÷ 4 × (0.001 in)².
- Resistivity. The National Bureau of Standards defines the annealed copper standard as 0.017241 ohm mm² per metre at 20°C, which is 1 ÷ 58 and corresponds to a conductivity of 58.0 MS/m.
- Temperature. NBS Handbook 100 gives the temperature coefficient of the standard copper as 0.00393 at 20°C, so R = R₂₀ × [1 + 0.00393 × (T − 20)].
| Wire size | Area (mm²) | Ω per 1,000 ft at 20°C | Ω per 1,000 ft at 75°C |
|---|---|---|---|
| 14 AWG | 2.08 | 2.525 | 3.071 |
| 12 AWG | 3.31 | 1.588 | 1.932 |
| 10 AWG | 5.26 | 0.9989 | 1.215 |
| 8 AWG | 8.37 | 0.6282 | 0.7640 |
| 6 AWG | 13.30 | 0.3951 | 0.4805 |
| 4 AWG | 21.15 | 0.2485 | 0.3022 |
| 2 AWG | 33.63 | 0.1563 | 0.1900 |
Worked examples
Single phase, 120 V, 15 A, 50 ft, 12 AWG at 75°C. The resistance is 1.932 Ω per 1,000 ft. The run is 50 ft out and 50 ft back, 100 ft in all, so R = 0.1932 Ω. Drop = 15 × 0.1932 = 2.90 V, which is 2.41% of 120 V. The load gets 117.10 V, and the cable wastes 15² × 0.1932 = 43.5 W. At 3% the smallest size is 12 AWG, since 14 AWG would lose 3.84%.
DC, 12 V, 10 A, 20 ft, 10 AWG at 75°C. Out and back is 40 ft: R = 1.215 × 40 ÷ 1,000 = 0.0486 Ω. Drop = 0.486 V, 4.05% of 12 V, so the load sees 11.51 V. On a 12 V circuit a few tenths of a volt matter, and 8 AWG is the smallest that keeps it under 3% (2.55%).
Three phase, 208 V, 30 A, 150 ft, 8 AWG at 75°C. R per conductor = 0.7640 × 150 ÷ 1,000 = 0.1146 Ω. Drop = √3 × 30 × 0.1146 = 5.95 V, 2.86%. The load sees 202.05 V, and the three conductors lose 3 × 30² × 0.1146 = 309 W.
Limits
- Resistance only. The reactance of AC cable adds to the drop, mostly in large cables, so a real figure can be higher.
- Copper only. Aluminium has a higher resistivity.
- Steady current. A motor draws several times its running current as it starts.
- Temperature. The default of 75°C is a common design assumption for a loaded cable. Enter 20°C for the resistance of a cool wire.
- Size is for drop only. Safe current capacity is a separate check.
Common mistakes
- Using the one-way length for the loop. In DC and single phase, the current travels out and back, so the calculator doubles the length for you.
- Mixing feet and metres. Check the unit.
- Forgetting the temperature. A hot cable has higher resistance than a cold one.
- Choosing a wire only by its current rating. A long run may need a larger wire to keep the drop small.
To turn power into current, use the watts to amps calculator, and for the running cost of a load the electricity cost calculator.
How it is calculated
Resistance, drop and power loss use exact decimal arithmetic, with 1 ft = 0.3048 m. Voltages are rounded to the cent, and the resistance shown to four significant figures.
Frequently asked questions
What is the voltage drop formula?
For DC and single phase circuits, drop = current × resistance of the wire per unit length × 2 × the one-way length, since the current goes out and comes back. For three phase it is √3 × current × resistance per unit length × length.
How is the wire resistance found?
From the cross-section of the wire and the resistivity of annealed copper, 1/58 ohm mm² per metre at 20°C. Resistance rises by 0.00393 of its 20°C value for each degree, so a hot cable drops more. A 12 AWG wire is 1.588 ohms per 1,000 feet at 20°C.
What voltage drop is acceptable?
It depends on the equipment and the rules where you live, so the calculator takes your own limit and shows the smallest wire that meets it. The default of 3% is an example, not a rule. Check the wiring regulations that apply to the installation.
Is a thicker wire always better?
For voltage drop, yes: a larger cross-section has less resistance, so less voltage and power are lost. Thicker wire costs more and is harder to install, so the choice is a balance.
Does the size it suggests mean the wire is safe?
No. The size is chosen for voltage drop only. The cable must also carry the current without overheating, which depends on the insulation, how it is installed and the wiring rules, and the protective device must suit it. Ask a qualified electrician.
What does this calculator leave out?
It counts only the resistance of copper. It ignores the reactance of AC cables, which matters for large cables and long runs, aluminium conductors, power factor and voltage-sensitive loads such as motors starting. Use it as an estimate.
Related calculators
- Amps to Watts CalculatorEnter the current and the voltage.
- Watts to Amps CalculatorEnter the power and the voltage.
- Electricity Cost CalculatorEnter each appliance's watts, the hours it runs each day and the days a year, with your price per kWh.
- Power ConverterEnter a power and choose the two units.
- Lumens to Watts ConverterEnter the light output in lumens and the efficacy of the bulb in lumens per watt.
- Length ConverterConvert any length or distance.
- Ohm's Law CalculatorChoose the two quantities you know and enter them.
- Resistor Color Code CalculatorChoose the colours of the bands to read the resistance, its tolerance and the lowest and highest value it can have.