Home Battery Sizing Calculator: How Many kWh and Ah Do You Need?
List your appliances with their watts and hours of use, and set your days of backup and battery details. You will see the energy used each day, the battery bank to buy in kWh and amp-hours, and how many batteries to wire.
Last reviewed
Battery bank to buy
8.22 kWh
342.6 Ah at 24 V, built from 8 batteries
- Energy used a day
- 3,700 Wh
- Taken from battery a day
- 4,111 Wh
- Usable from the bank
- 4,111 Wh
- All loads together
- 535 W
- In series × parallel
- 2 × 4
- Installed capacity
- 9.60 kWh
Choose an inverter that covers all the loads running together, plus the starting surge of motors. This tool sizes the battery only and ignores aging, so leave some margin.
How big a battery do you need?
A battery bank has to hold enough energy to run your appliances for as long as you want to go without a charge, after allowing for what you lose on the way. Three losses matter. The inverter wastes some energy turning battery current into mains current. A battery should not be drained completely, so only a part of its rating is usable. And in cold weather a battery gives less than its rating.
This calculator starts from your appliances, applies each of those allowances, and ends with a bank size in kWh and amp-hours and the number of batteries to buy.
The calculation
- Energy used a day = the sum of watts × hours of use × quantity, for every appliance, in watt-hours.
- Energy drawn from the battery = energy used ÷ inverter efficiency + any direct DC use.
- Bank capacity (Wh) = energy drawn × days of backup ÷ (cold-weather factor × depth of discharge).
- Bank capacity (Ah) = bank capacity (Wh) ÷ system voltage.
- Batteries = batteries in series (system voltage ÷ one battery’s voltage, rounded up) × strings in parallel (bank Ah ÷ one battery’s Ah, rounded up).
The same chain is set out in a step-by-step guide to off-grid battery banks from Coule Energy: daily load, then inverter efficiency, then days of autonomy, then temperature derating, then depth of discharge, then division by system voltage. Its worked example, 5 kWh a day of AC load plus 0.3 kWh of DC, 3 days, 90% inverter efficiency, 90% temperature factor, 50% depth of discharge and 48 V, is printed as 815 Ah. Our calculator gives 813.3 Ah for those inputs, and the gap is in the guide, not here. The guide rounds each step: 5.56 kWh, 5.86, 17.58, then 17.58 ÷ 0.9 = 19.533 printed as 19.54, then 39.08 kWh. Dividing that 39.08 kWh by 48 V gives 814.2 Ah, not the 815 shown, so the printed figure is off by a further rounding slip. Carrying the exact values through every step, as this calculator does, gives 39,037 Wh and 813.27 Ah, which is 0.2% below the printed figure.
Worked example
These appliances are examples only: six 10 W lights for 5 hours, three 75 W fans for 8 hours, a 150 W fridge that runs 8 hours in the day, and a 100 W television for 4 hours.
- Energy used = 6 × 10 × 5 + 3 × 75 × 8 + 150 × 8 + 100 × 4 = 300 + 1,800 + 1,200 + 400 = 3,700 Wh a day.
- At 90% inverter efficiency the battery supplies 3,700 ÷ 0.9 = 4,111.11 Wh.
- For one day of backup at 50% depth of discharge and no cold-weather correction the bank must be 4,111.11 ÷ 0.5 = 8,222.22 Wh.
- On a 24 V system that is 8,222.22 ÷ 24 = 342.59 Ah.
- With 12 V, 100 Ah batteries you need 2 in series and 4 strings in parallel, which is 8 batteries and 9.6 kWh installed.
- All loads running together draw 60 + 225 + 150 + 100 = 535 W, so the inverter must handle at least that, plus motor surges.
Why depth of discharge matters
Same load of 3,700 Wh a day, 90% inverter, one day of backup, 24 V.
| Depth of discharge | Bank capacity (Wh) | Bank capacity (Ah) |
|---|---|---|
| 50% | 8,222.22 | 342.59 |
| 60% | 6,851.85 | 285.49 |
| 70% | 5,873.02 | 244.71 |
| 80% | 5,138.89 | 214.12 |
| 90% | 4,567.90 | 190.33 |
The depth of discharge you can safely use depends on the battery type, so use the figure from the maker’s datasheet. The Coule Energy guide gives 50% to 80% for lead-acid batteries and says never to go beyond 80%, because drawing them down further shortens their life.
Points to check
- Hours are averages. A fridge runs only part of the day. Use the hours it actually runs, not 24, or the bank comes out far too large.
- Include every load you need. Leave out what you can live without in an outage and you will save a lot of battery.
- Add margin for aging. Batteries lose capacity over the years. This tool sizes for new batteries.
- Check the voltage. The system voltage is set by the inverter. Higher voltage means lower current in the cables.
- Safety. Battery banks store a lot of energy. Have a qualified installer connect and protect them.
Related tools: the generator sizing calculator, the solar panel payback calculator, the electricity cost calculator and the watts to amps calculator.
Frequently asked questions
How do I calculate the battery size I need?
Add up watts × hours for every appliance to get watt-hours a day, divide by the inverter efficiency, multiply by the days of backup, and divide by the depth of discharge. Divide the result by the system voltage to get amp-hours. The calculator does all of this.
What is depth of discharge?
It is the share of a battery’s rated capacity you are willing to use before recharging. Using less of the capacity makes batteries last longer but means a bigger bank. Use the figure on the battery maker’s datasheet for your type of battery.
How many days of backup should I choose?
Choose the number of days you want to run without any charging from the grid or solar. One day covers a long outage or a cloudy day. Off-grid systems often choose more. More days means a proportionally bigger and costlier bank.
What is the cold-weather factor?
Batteries deliver less than their rating when cold. The factor is the share of rated capacity available, so 90 means 90%. Leave it at 100 in a warm room, and use the maker’s data if the batteries sit somewhere cold.
How are the number of batteries worked out?
Batteries in series add voltage, so the system voltage divided by one battery’s voltage, rounded up, gives the batteries per string. Strings in parallel add amp-hours, so the bank’s amp-hours divided by one battery’s amp-hours, rounded up, gives the number of strings.
Does the result include the inverter size?
No. It shows the total watts of all appliances together as a lower limit, but the inverter must also handle motor starting surges. Use the generator sizing calculator to work out surge loads, and ask an installer to choose the inverter.
Related calculators
- Generator Sizing CalculatorList your appliances with their running watts, starting watts and quantity.
- Solar Panel Payback CalculatorEnter the system size and cost, the yearly yield for your site and the price of grid electricity.
- Electricity Cost CalculatorEnter each appliance's watts, the hours it runs each day and the days a year, with your price per kWh.
- Watts to Amps CalculatorEnter the power and the voltage.
- Amps to Watts CalculatorEnter the current and the voltage.
- Voltage Drop CalculatorEnter the supply voltage, the current, the one-way length and the wire size.